Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Still deciding? Get samples of US$ 200/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
NO. | ITEM | UNIT | VALUE | ||
1 | Rated voltage | kV | 40.5 | ||
2 | Rated insulation level | Power frequency withstand voltage | Dry type | kV | 95 |
Wet type | kV | 80 | |||
Lightning impulse withstand voltage (peak) | kV | 185 | |||
3 | Rated current | A | 1250,1600, 2000 | ||
4 | Rated short-circuit breaking current | kA | 20, 25, 31.5 | ||
5 | Rated operating sequence | Opening-0.30 closing/opening -180 closing/opening | |||
6 | Rated short-circuit breaking current frequency | times | 12 | ||
7 | Rated short-circuit closing current (peak) | kA | 50, 63, 80 | ||
8 | Rated peak withstand current | kA | 50, 63, 80 | ||
9 | Rated short-time withstand current | kA | 20, 25, 31.5 | ||
10 | Rated short-circuit duration current | s | 4 | ||
11 | Average opening speed | m/s | 1.5±0.2 | ||
12 | Average closing speed | m/s | 0.7±0.2 | ||
13 | Contact closing bounce time | s | ≤2 | ||
14 | Three-phase closing (opening) synchronization time difference | s | ≤2 | ||
15 | Closing time | s | ≤150 | ||
16 | Opening time | s | ≤60 | ||
17 | Mechanical life | times | 10000 | ||
18 | Rated operating voltage and auxiliary circuit rated voltage | V | DC/AC220, 110, 24 | ||
19 | DC resistance per phase circuit (excluding transformers) | μΩ | ≤100 | ||
20 | Allowable wear thickness of dynamic and static contacts | mm | 3 | ||
21 | Weight | kg | 800 |